Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/30/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 03/25/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) METAL NOT AN APPROVED EXTENDER RING 2) WE HAVE MULTI-POLE TERMINATION UNDER A LUG 3) USED ANTI-OXIDE COMPOUND ON ALL ALUMINIUM TERMINATIONS 4) WHERE ARE GROUND RODS ? 5) SEPERATE GROUNDS AND NEUTRALS AT SUB PNAEL 250.24 |
| 12/08/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED GROUND WIRE FROM RODS UNSPLICED TO SERVICE. PLANS CALL FOR 200A ALL IN ONES FOR EACH |