Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/15/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/12/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CONDENSATE DRAIN, OPEN VENT FOLLOWS TRAP, NOT AHEAD OF IT. DO NOT NEED TO PAINT COPPER, ONLY PVC 2) CONTROL WIRING, EXPOSED TO RUN NEEDS TO BE IN FLEX, OR CONDUIT (ALL UNITS) 3) MARK DATA PLATE IF AUX HT STRIP AS USED. MARK OUT PLATE IF NONE 4) PROVIDE SUN SHEILD COVERS, FLEX DUCT CONNECTORS |