Permit: T03CM02563

Parcel: 122154490

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/15/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
12/12/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) CONDENSATE DRAIN, OPEN VENT FOLLOWS TRAP, NOT AHEAD OF IT. DO NOT NEED TO PAINT COPPER, ONLY PVC 2) CONTROL WIRING, EXPOSED TO RUN NEEDS TO BE IN FLEX, OR CONDUIT (ALL UNITS) 3) MARK DATA PLATE IF AUX HT STRIP AS USED. MARK OUT PLATE IF NONE 4) PROVIDE SUN SHEILD COVERS, FLEX DUCT CONNECTORS