Inspection History Details
Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
Permit Number - T03CM02550
Inspection Description - SHEET ROCK NAILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2003 | SHEET ROCK NAILING | Approved | IVRS - Inspection 0000* | |
| 11/10/2003 | SHEET ROCK NAILING | Denied | IVRS - Inspection 0999*/ 1) SAG RESISTANT DRYWLL REQUIRED AT ALL CEILINGS. 2) DRYWALL 3/4" MAX. ON SOLE PLATES. 3) 8" NAIL SPACING MAX. ON WALLS - 12" WITH SCREWS. 4) NAIL CORNER AT KITCHEN LID, WALL EDGES. 5) NAIL EDGES THROUGHOUT. 6) INSTALL SOFFIT BOARD AT FRONT EXTERIOR. |