Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T03CM02535

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/13/2004 BUILDING - FINAL Approved IVRS - Inspection 0000*
02/10/2004 BUILDING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) CHANGE OUT 70 AMP BREAKER TO 100 AMP #2 AL.=OK 2) CLEAN UP T & P, SUPPORT EXPANSION TANK
01/29/2004 BUILDING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) EXPANSION TANK NOT SUPPORTED 2) T.P. LINE TO HAVE POSITIVE FLOW, PITCH 3) RESOLVE SCHEDULE 40 SWEEP AT SERVICE 4) LABEL METERS
01/28/2004 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) NO PERMANENT ADDRESS 2) NO PLANS OR PERMIT 3) HOUSE HAS BEEN OCCUPIED 4) TO MANY PERSONAL ITEMS IN GARAGE TO INSPECT 5) PROVIDE ROOF ACCESS
01/21/2004 BUILDING - FINAL Not ready for Inspection 1) LABEL OUTSIDE OF SERVICE EQUIPMENT FOR IT'S USE (DISCONNECT) 2) PLUG HOLE IN BOTTOM OF PANEL 3) USE ONLY SCHEDULE 80 NON-METALLIC CONDUIT 4) CANNOT FIND OUTLETS IN GARAGE, A/C UNIT NOT INSTALLED 5) MISSING HOSE BIB ANTI-SIPHONS 6) REAR WALL 1ST FLOOR SOME TYPE OF EXHAUST DUCT, NO TERMINATION 7) SUPPORT EXPANSION TANK 8) TWO OUTLETS IN REAR BEDROOM, NO POWER 9) GFCI OUTLETS NOT WORKING 1ST FLOOR KITCHEN COUNTER 10) CONDENSATE LINE AT KITCHEN NOT CONNECTED, ALSO AT 1ST FLOOR LAV CABINET 11) DISHWASHER DRAIN LINE, LOOP UP ABOVE DRAIN BOARD 12) LABEL NOT MARKED FOR A/C UNIT ON ROOF OVER CURRENT PROTECTION 13) 2-3/4" PIPES OPEN TO WEATHER 14) SEAL ROOF JACKS FUTURE COOLER