Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/17/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 07/16/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) DWV'S FAILED WATER TEST 2) REMOVE SCREEN FROM DRYER VENT AND NAIL PROTECT 3) EXHAUST FAN IN HALL BATH MISSING FLAPPER |
| 07/15/2003 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) COMPLETE NAIL LATH AND RECALL |