Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T03CM02487
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2003 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
07/11/2003 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) FINISH PIPING CHILLER LINES AND CONDENSATE DRAIN LINES TO FAN COIL. CONDENSATE CANNOT TERMINATE INTO A SINK TAIL PIECE. CONNECTION TO A LAV. TAIL PIECE WOULD BE ACCEPTABLE. FINISH DUCTING | |
06/25/2003 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) INSPECTED STAINLESS STEEL EXHAUST DUCT. STILL NEED TO SEE FINAL CONNECTION AND HOODS. CHECKED MAKEUP AIR DUCTS. PLANS SHOW FIRE DAMPERS IN A/C DUCTS. THERE ARE NO FIRE RATED WALLS OR CEILINGS BEING PENETRATED. CHECKED CONDENSATE DRAIN LINE. CONFIRMED FIRE DAMPER ACCESS DOORS ON 2ND FLOOR, OK FOR CEILING TILES. LEAVE OUT IN LAB |