Permit: T03CM02487

Parcel: 12709001E

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T03CM02487

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2003 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*
07/11/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) FINISH PIPING CHILLER LINES AND CONDENSATE DRAIN LINES TO FAN COIL. CONDENSATE CANNOT TERMINATE INTO A SINK TAIL PIECE. CONNECTION TO A LAV. TAIL PIECE WOULD BE ACCEPTABLE. FINISH DUCTING
06/25/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) INSPECTED STAINLESS STEEL EXHAUST DUCT. STILL NEED TO SEE FINAL CONNECTION AND HOODS. CHECKED MAKEUP AIR DUCTS. PLANS SHOW FIRE DAMPERS IN A/C DUCTS. THERE ARE NO FIRE RATED WALLS OR CEILINGS BEING PENETRATED. CHECKED CONDENSATE DRAIN LINE. CONFIRMED FIRE DAMPER ACCESS DOORS ON 2ND FLOOR, OK FOR CEILING TILES. LEAVE OUT IN LAB