Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T03CM02470
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2004 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000*/ 1) DUCT SMOKE DETECTORS ONLY REQUIRED IN RTU-2 + 4. SEE SECTION 606.2 2000 IMC. INSPECTED ALL DUCT AND DIFFUSERS. OK FOR CEILING TILES. LEAVE OUT A TILE UNDER EACH DUCT DETECTOR | |
01/22/2004 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ INSPECTED JOINTS ON SUSPENDED ROUGH DUCT. OK TO INSULATE. CHECKED SUPPLY AND EXHAUST IN RESTROOMS. OK TO COVER. |