Permit: T03CM02470

Parcel: 133552300


Addresses:

1145 S HARRISON RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T03CM02470

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/05/2004 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*/ 1) DUCT SMOKE DETECTORS ONLY REQUIRED IN RTU-2 + 4. SEE SECTION 606.2 2000 IMC. INSPECTED ALL DUCT AND DIFFUSERS. OK FOR CEILING TILES. LEAVE OUT A TILE UNDER EACH DUCT DETECTOR
01/22/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ INSPECTED JOINTS ON SUSPENDED ROUGH DUCT. OK TO INSULATE. CHECKED SUPPLY AND EXHAUST IN RESTROOMS. OK TO COVER.