Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/10/2004 |
BUILDING ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 02/09/2004 |
BUILDING ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999* SEE NOTES FROM 2/5/04 |
| 02/05/2004 |
BUILDING ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999* 1) CARRYING TRACK ON BOTH SIDES OF LIGHT FIXTURES TO BE SUPPORTED BY 4' OC MAX. 2) ANY WIRE WITHA SLOPE OF MORE THAN 1/6 REQUIRES A COUNTER SLOPE WIRE. 3) POP RIVETS ARE NOT USEFUL AS SUPPORTS FOR GRID |
| 01/22/2004 |
BUILDING ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 01/16/2004 |
BUILDING ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* INSULATION OK- HARD LIDS OK. RECALL WHEN CEILING GRID IN. |