Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
Permit Number - T03CM02470
Inspection Description - BUILDING ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/10/2004 | BUILDING ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
02/09/2004 | BUILDING ABOVE CEILING | Denied | IVRS - Inspection 0999* SEE NOTES FROM 2/5/04 | |
02/05/2004 | BUILDING ABOVE CEILING | Denied | IVRS - Inspection 0999* 1) CARRYING TRACK ON BOTH SIDES OF LIGHT FIXTURES TO BE SUPPORTED BY 4' OC MAX. 2) ANY WIRE WITHA SLOPE OF MORE THAN 1/6 REQUIRES A COUNTER SLOPE WIRE. 3) POP RIVETS ARE NOT USEFUL AS SUPPORTS FOR GRID | |
01/22/2004 | BUILDING ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000* | |
01/16/2004 | BUILDING ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* INSULATION OK- HARD LIDS OK. RECALL WHEN CEILING GRID IN. |