Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/29/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK C OF O |
| 10/28/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ NOTES: 1) DISCONNECT BRACES NEED TO BE SECURED TO ROOFTOP WITH PROPER HARDWARE. 2) FLEX CONNECTOR NOT INSTALLED PROPERLY AT WEST UNIT. 3) DISCONNECT ON EAST UNIT NEEDS 36" IN FRONT FOR DEDICATED WORKING CLEARANCE - 110-26 NEC. 4) LABEL DISCONNECTS. 5) INSTALL REJECTION PINS IN SERVICE DISC. SW. |
| 10/22/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ NOTES: 1) INSTALL PERMANENT PANEL SCHEDULES. 2) HAVE LADDER ON SITE FOR ROOF INSPECTION. |
| 09/18/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/1) I.D. CIRCUIT BREAKERS IN PANEL AT SERVICE. |