Permit: T03CM02464

Parcel: 13824182A


Addresses:

1620 W COMMERCE CT

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
09/15/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
09/12/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*/ 1) NOTES: CONDUITS SUPPORTED WITH SIZMIC WIRES MUST BE TIED OFF BOTH ENDS 2) SIZMICS FOR 2 X 4 LAY IN FIXTURES MUST HAVE AT LEAST 3 TURNS OF WRAP. RECALL WHEN DONE
09/10/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*/ NOTES: 1) ALL GRID FIXTURES NEED SIZMIC WIRES. 2) SUPPORT CONDUIT PER NEC. 3) SUPPORT FLEX PER NEC. 4) COMPLETE MAKE-UP IN J-BOXES.
09/05/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection