Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM02451
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :*/INSPECTED AS PARTIALS. WILL SEE REST OF WATER HEATERS & MIXING VALVE AT FINAL | |
09/02/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :INSULATION ON HOT AND HOT RETURN PIPING OK PER LETTER FROM ALLAN N JOHNSON P.E. | |
08/25/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/PARTIAL 03035-PSI AIR TEST ON H2O PIPING IN WALL AND OVERHEAD OK PROVIDE INSULATION PER PLAN ON HOT & COLD PIPING 03036-WAITING ON INSULATION ISSUE 03050- 15 PSI AIR TEST ON GAS SYSTEM (PARTIAL) TO WATER HEATER AREA, DRYERS 2) AND 8 AHV'S. WATER HEATER DRYERS, AND AHV'S PIPING IS CLOSE BUT NEEDS TO BE TIED IN AND RETESTED. 1) NEED RE LINE & REVISED GAS ISOMETRIC BECAUSE OF CHANGE IN GAS LINE SIZING |
|
08/06/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) 80 PSI AIR TEST ON IN WALL ONLY ON WATER PIPING OK 2) WATER TEST AND AIR TEST ON WASTE AND VENT THRU ROOF OK EXCEPT EYE WASH VENT NEED TO BE 2" 3) OVERHEAD PIPING TO BE SUPPORTED CORRECTLY | |
08/03/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) AIR TEST ALL PIPING |