Permit: T03CM02451

Parcel: 128102930

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T03CM02451

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
10/19/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*/REVISED PLAN ON SITE
09/13/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :* NOT READY
09/08/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/2" DRAIN FOR EMERGENCY EYE WASH IN POOL EQUIP. ROOM WATER TEST . WASTE & VENT THRU ROOF OK PENDING REVISED CITY APP. PLAN WITH ADDITION OF THIS FIXTURE
07/13/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/ 1) WATER TEST ON 4" POOL EQUIPMENT FLOOR DRAIN OR SINK UNDERGROUND OK
05/10/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/ 4" BLD SEWER TIE TOGETHER ON WEST SIDE OF GATE HOUSE PER PLAN INITIALED ON 5/10/04 WTR TEST OK.
04/12/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ REVISED CITY APPROVED DRAWING ON SITE SHOWING RED LINE INSTALLATION.
04/08/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/
04/02/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 6PSI AIR TEST ON WASTE AND VENT UNDERGROUND ONLY ROOMS 137-140, UP TO TEST WYE, JUST BEFORE ROOM 136. NEED TO TERMINATE END OF LINE 4" CLEAN OUTS VERTICAL AND ADD DRAIN FOR LAV IN ROOM 139.
03/16/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*
03/10/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ WTR TEST ON 4" FLOOR DRAIN FOR WASHING MACHINE AREA WITH 2" VENT PARTIAL APPROVAL PENDING CITY APPROVED DRAWING SHOWING SIZE AND ACTUAL INSTALLATION. COVER AT YOUR OWN RISK. (GATE HOUSE)
03/09/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 8" SITE SEWER WTR TEST FROM MANHOLE INSTALLED PER PLAN AS HIGHLIGHTED ON CV-1 OK. WILL NEED VERIFICATION OF GRADE. / 2" H2O STUBBED OUT OF UNDER BLD SLAB OUTSIDE 4' AT MECH ROOM #157. 100 PSI TEST PARTIAL APPROVEL PENDING CITY APPROVED DRAWING SHOWING CHANGE IN LOCATION.
03/05/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ GATE HOUSE EAST END UNDERGROUND FOR WASHING MACHINE ROOM, AND MECH. ROOM.
03/02/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ GREASE WASTE FOR KITCHEN AREA AIR TEST UNDERGROUND PARTIAL APPROVAL WILL REQUIRE CITY APPROVED DRAWING OF INSTALLATION AND GREASE TRAP ORIENTATION. 4" SANITARY SEWER IN GATE HOUSE PARTIAL APPROVAL AIR TEST WILL NEED TO SEE POOL EQUIPMENT AREA, WTR HTR ROOM AND MAIN LAUNDRY ROOM.
03/01/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/ 1) INSTALL PER PLAN OR HAVE CITY APPROVED PLAN SHOWING INSTALLATION 2) HUB DRAIN ARE NOT APPROVED SANITARY DRAIN RECEPTORS. PROVIDE APPROVED DRAIN RECEPTORS. 3) FULL SIZE CLEANOUTS WILL BE REQUIRED ON HORIZONTAL DRAINAGE 4) AIR TEST ON TRUNK SEWER PARTIAL APPROVAL FOR BACKFILL