Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM02445
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* ROOMS 258, 259, 261, 262 AN INST HOT IN BREAKROOM | |
11/12/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1) FINISH SUPPORTING VDV CABLES UP OFF GRID. 2) FINISH ITEM #3 OF INSP 10/27/03 | |
10/27/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
10/07/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) INSTALL HOT WATER HEATER IS A 3KW-120V UNIT-THIS REQUIRES A 25 AMP CIRCUIT. UNIT IS NOT LISTED FOR CORD CONNECTION. PLEASE PRVOIDE A DISCONNECTING MEANS | |
08/27/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) BOND BUSHING NEEDED AT CONCENTRIC OVER 250V 250-97 2) WE HAVE MULTIPLE TERMANATIONS AT LINE TERMANEL-LIEBERT UNIT 3) OK PHASE I AND II AS NOTED |