Permit: T03CM02445

Parcel: 133231480


Addresses:

7202 E ROSEWOOD ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/14/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* ROOMS 258, 259, 261, 262 AN INST HOT IN BREAKROOM
11/12/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) FINISH SUPPORTING VDV CABLES UP OFF GRID. 2) FINISH ITEM #3 OF INSP 10/27/03
10/27/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
10/07/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) INSTALL HOT WATER HEATER IS A 3KW-120V UNIT-THIS REQUIRES A 25 AMP CIRCUIT. UNIT IS NOT LISTED FOR CORD CONNECTION. PLEASE PRVOIDE A DISCONNECTING MEANS
08/27/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) BOND BUSHING NEEDED AT CONCENTRIC OVER 250V 250-97 2) WE HAVE MULTIPLE TERMANATIONS AT LINE TERMANEL-LIEBERT UNIT 3) OK PHASE I AND II AS NOTED