Permit: T03CM02437


Addresses:

1095 S TYNDALL AV


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T03CM02437

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2004 PLUMBING - ROUGH, SOIL Approved 1) SOIL WATER IS OK 2) NOTE: MUST RED LINE APPROVED PLANS SHOWING LOCATION AND EXIST OF BLDG. DRAIN PRIOR TO NEXT INSPECTION
02/10/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 1) SOIL WTR TEST IS OK. 2) OK TO BACKFILL TRENCH. 3) NOTE: CLOSET BENDS HAVE NOT BEEN INSTALLED AT THIS TIME. SYSTEM WILL REQUIRE ANOTHER WTR TEST AND CLOSET BENDS EXPOSED AT TIME OF INSPECTION.
02/09/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/ 1) CANNOT HAVE A BUSHING IN A HORIZONTAL POSITION, SEE SEC 315.5 - 94 UPC INTERPRETATION. 2) RE-TEST SYSTEM.