Permit: T03CM02437


Addresses:

1095 S TYNDALL AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM02437

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FOR C OF O
12/08/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/PARKING LOT LIGHTING STILL NOT IN COMPLIANCE WITH COT LIGHTING ORDINANCE. ALSO SPLICES ARE EXPOSED AT TOP OF POLE, NO GROUND WIRE RUN TO FIXTAURE. SEE SHEET. PER NEC 90-2 - 370-17 COT LIGHTING ORDIN. ANY ? CALL RAY M. 791-5550 EXT 1136 NOTE: POLES ON PRIVATE PROPERTY
12/01/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PERMIT CARD MUST BE POSTED ON SITE
2) OUTSIDE PARKING POLE LTS NOT WIRED PER CODE, AT TOP OF POLE-EXPOSED SPLICES AND WIRING MUST BE IN APPROVED RACEWAY AND J-BOX
3) TYPE OF LIGHT FIXTURE IN VIOLATION OF CITY OF TUCSON LIGHTING ORDINANCE FOR OUTSIDE LIGHTING. SEE SHEET