Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM02437
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FOR C OF O |
|
| 12/08/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/PARKING LOT LIGHTING STILL NOT IN COMPLIANCE WITH COT LIGHTING ORDINANCE. ALSO SPLICES ARE EXPOSED AT TOP OF POLE, NO GROUND WIRE RUN TO FIXTAURE. SEE SHEET. PER NEC 90-2 - 370-17 COT LIGHTING ORDIN. ANY ? CALL RAY M. 791-5550 EXT 1136 NOTE: POLES ON PRIVATE PROPERTY |
|
| 12/01/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PERMIT CARD MUST BE POSTED ON SITE 2) OUTSIDE PARKING POLE LTS NOT WIRED PER CODE, AT TOP OF POLE-EXPOSED SPLICES AND WIRING MUST BE IN APPROVED RACEWAY AND J-BOX 3) TYPE OF LIGHT FIXTURE IN VIOLATION OF CITY OF TUCSON LIGHTING ORDINANCE FOR OUTSIDE LIGHTING. SEE SHEET |