Permit: T03CM02437


Addresses:

1095 S TYNDALL AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/17/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/14/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ MC CABLE ABOVE ENTRY DOOR STILL NOT SUPPORTED.
06/10/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
06/08/2004 ELECTRIC - INTERMEDIATE Denied 1) SUPPORT EMT WITHIN 3' OF TERMINATION. 2) SUPPORT J-BOXES PER NEC. 3) SUPPORT MC CABLE WITHIN 12" EACH TERMINATION AND AT INTERVALS NOT TO EXCEED 6' PER NEC. 4) SELF TAPPING SCREW NOT APPROVED FOR BLD STEEL GROUNDING CONNECTION OF LUG. ALSO SCRAPE OFF PAINT UNDER LUG. PER ART 250 NEC.