Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM02437
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/14/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ MC CABLE ABOVE ENTRY DOOR STILL NOT SUPPORTED. |
|
| 06/10/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 06/08/2004 | ELECTRIC - INTERMEDIATE | Denied | 1) SUPPORT EMT WITHIN 3' OF TERMINATION. 2) SUPPORT J-BOXES PER NEC. 3) SUPPORT MC CABLE WITHIN 12" EACH TERMINATION AND AT INTERVALS NOT TO EXCEED 6' PER NEC. 4) SELF TAPPING SCREW NOT APPROVED FOR BLD STEEL GROUNDING CONNECTION OF LUG. ALSO SCRAPE OFF PAINT UNDER LUG. PER ART 250 NEC. |