Permit: T03CM02424

Parcel: 128102930

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM02424

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/OK FOR FINAL C/O
11/30/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/1ST FLR. WATER HTR ROOM, INSUFFICENT CLEARANCE, A/H 13 - COND. DRAIN -DOTOR? PLATE
11/29/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/LABEL ALL HEAT STRIPS & FAN COILS. PROVIDE BUSHINGS ON PACKING AT REFER LINE PENETRATIONS THRU CABINET. AH-16 PROVIDE CONDENSATE DRAIN
11/24/2004 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
11/22/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/RELOCATE TRAPS ON CONDENSATE DRAINS BLOCKING FILTER ACCESS. 3RD FLOOR A/C 14 PROVIDE ACCESS TO DAMPER. 3RD FLOOR A/C 15 PROVIDE ACCESS TO DAMPER. A/C 16 PROVIDE CONDENSATE DRAIN. REPLACE ALL 6X6 DAMPER ACCESS DOORS W/FULL DUCT SIZE DOORS.
08/06/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/ 1) NEED TO SEE FIREPLACE VENT PIPES ALL FLOORS 2) PROVIDE SHEET ROCK ON FLOORS OF PLENIUMS 3) DO NOT COVER ANY WORK PRIOR TO INSPECTIONS 4) OK TO SHEETROCK 2ND FLOOR BATHROOMS