Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/01/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :*/OK FOR FINAL C/O |
| 11/30/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :*/1ST FLR. WATER HTR ROOM, INSUFFICENT CLEARANCE, A/H 13 - COND. DRAIN -DOTOR? PLATE |
| 11/29/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :*/LABEL ALL HEAT STRIPS & FAN COILS. PROVIDE BUSHINGS ON PACKING AT REFER LINE PENETRATIONS THRU CABINET. AH-16 PROVIDE CONDENSATE DRAIN |
| 11/24/2004 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 11/22/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :*/RELOCATE TRAPS ON CONDENSATE DRAINS BLOCKING FILTER ACCESS. 3RD FLOOR A/C 14 PROVIDE ACCESS TO DAMPER. 3RD FLOOR A/C 15 PROVIDE ACCESS TO DAMPER. A/C 16 PROVIDE CONDENSATE DRAIN. REPLACE ALL 6X6 DAMPER ACCESS DOORS W/FULL DUCT SIZE DOORS. |
| 08/06/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) NEED TO SEE FIREPLACE VENT PIPES ALL FLOORS 2) PROVIDE SHEET ROCK ON FLOORS OF PLENIUMS 3) DO NOT COVER ANY WORK PRIOR TO INSPECTIONS 4) OK TO SHEETROCK 2ND FLOOR BATHROOMS |