Permit: T03CM02424

Parcel: 128102930

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T03CM02424

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/18/2004 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*/OK TO CLOSE SHAFT C=3 4TH FLOOR. C-6 4TH FLOOR PROVIDE ACCESS PANEL. OK 3RD FLOOR SOFFIT OK TO CLOSE WATER HEATER SHAFT 2ND FLOOR. OK SHAFT WATER HEATER VENTS? RTH FLOOR
11/15/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/4TH FLOOR SHAFT C-6 ANGLE TO THIN AT BOTTOM DAMPER. ANGLE NOT FLUSH TO WALL TOP DAMPER & NOT FLUSH ON TOP SIDE OF DAMPER. PROVIDE ACCESS DOOR. DHAFT C-3 USE PROPER SLEEVE & ANGLE IRON FRAME ON LOWER DAMPER. PROVIDE CLEARANCE AROUND WATER HEATER VENT 4TH FLOOR
11/05/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/OK TO CLOSE SHAFT C-2 2ND FLOOR, C-4 3RD FLOOR, C-4 4TH FLOOR, SEAL AROUND OUTER ANGLE IRON C-4 OK. WATER HEATER SHAFT 4TH FLOOR, C-1 4TH FLOOR, C-2 4TH FLOOR C-5 4TH FLOOR. SEAT SADDLE TAPS ON WATER HEATER VENTS. PROVIDE ANGLE IRON ON FIRE DAMPER C-3 4TH FLOOR. FRAME DAMPERS C-6 4TH FLOOR, 3RD FLOOR
10/29/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/1)OK SHEET ROCK 327, 328, 329, 130, 131, 132, 230, 231, 232, 330, 331, 332. 2)OK TO SHEET ROCK SHAFT C-1 2ND FLOOR C-6 2ND FLOOR LAUNDRY ROOM 2ND FLOOR, SHAFT C-3 2ND FLOOR, CHAFT C-4 2ND FL. SHAFT C-5 2ND FLOOR & 3RD FLOOR, CHAFT C-4 3RD FLOOR, C-6 3RD FLOOR FRAME SHAFT WALL FOR FIRE DAMPER. OK SHAFT C-1 3RD FLOOR, OK SOFFITS 4TH FLOOR
10/21/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/OK TO SHEET ROCK 1ST, 2ND FLOOR SOFFITS. OK 3RD FLOOR EXCEPT EAST MIDDLE EQUIPMENT ROOM. EAST MIDDLE & WEST END 4TH FLOOR NOT READY. OK FOR 4TH FLOOR MIDDLE. OK FOR TEMP C/O FOR STOCKING FURNITURE
10/11/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/DISCUSSED FIRE DAMPER ISSUES
10/01/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) VENTS ON CONDENSATE TRAPS MUST BE DOWNSTREAM OF TRAP
09/23/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) INSPECTED DRYER VENTS OK TO COVER 2) DISCUSSED FIRE DAMPER OPENINGS
09/21/2004 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/16/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/INSPECTED FIRE DAMPERS IN ELEVATOR EQUIPMENT ROOM. OK TO SHEET ROCK
09/15/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/1)REMOVE WOOD NEAR ELEVATOR EQUIPMENT FIRE DAMPERS. FINISH SHEET ROCK & PROVIDE ANGLE IRON. 2)PROVIDE MIN. 2" CLEARANCE FROM COMBUSTIBLES ON DRYER VENTS.
09/10/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) INSPECTED BATHROOM EXHAUST AND VENTILATOR FANS ON 4TH FLOOR OK TO SHEET ROCK LIDS
08/17/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) CHECKED CONDENSATE DRAIN LINES. OK TO COVER ALL FLOORS
08/12/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) INSPECTED ALL FIREPLACE FLUE PIPES. OK TO COVER
08/11/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/1)PROVIDE SCREWS IN JOINTS ON FIREPLACE FLUE PIPE & MIN. 1" CLEARANCE FROM COMBUSTBLES.2) EXPOSE ALL FLUE PIPES ON 1ST AND 2ND FLOORS FOR INSPECTION. 3) INSPECTED EXHAUST DUCTS, FAN COILS, FIREPLACES. OK FOR SHEET ROCK 3RD FLOOR SUITES.
07/27/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*PARTIAL APPROVAL. PARTIAL INSPECTION IN GATE HOUSE. OK TO START SHEET ROCK ON WALLS.
07/12/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) CHECK WITH MANUFACTURER FOR LISTING ACCEPT 6" RED T0 4" DISCHARGE 2) ROOM IS GOING TO BE A RETURN AIR PLENIUM. ALL ? CONTAINED WITHIN MUST HAVE LISTED FLAME SMOKE RATING FOR PLENIUM
07/07/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) JOB AS LAYED OUT HAS AIR HANDLER IN A PLENIUM, RETURN AIR DRAWN THRU LOWERED DOOR INTO EVAPORATOR. NO COMBUSTIBLES ALLOWED IN PLENIUM RETURN WITHOUT PROPER 25/50 FLAME SMOKE RATING 2) DUCT RETURN THRU DOOR/PANEL INTO EVAP COIL