Permit: T03CM02424

Parcel: 128102930

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T03CM02424

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
11/23/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
11/02/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*/GAS AT HOTEL IS COMPLETE AND ONLY FINAL OR BONDING REQUIRED FOR GAS CARD. GAS AT GATE HOUSE IS COMPLETE AND ONLY FINAL OR BONDING REQUIRED FOR GAS CARD. POOL EQUIP AREA REQUIRES COMPLETION OF GAS PIPING AND TESTING. (OR TEMP C OF O FOR STOCKING) 3RD FLOOR FIXTURES IN ROOMS OK.
11/01/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*/ 1) GATE HOUSE 15 PSI TEST TYO WATER HEATERS AND DRYERS OK 2) NEED CORRECT INSTALLATION OF GAS REGULATOR FOR THIS AND COMPLETETION OF POOL EQUIPMENT GAS PIPING 2) INSTALL GAS PIPING TO HOTEL WATER HEATERS PER YOUR CITY APPROVED PLAN
10/19/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*/NEED TEST AT POOL EQUIP STUB UP T POOL EQUIP AND TO SEE ALL REGULATORS & NEED TO SEE GATE HOUSE WATER HEATERS & HOTEL WATER HEATERS
10/05/2004 PLUMBING - GAS PRESSURE TEST Partial Approval MED. PRESSURE LINE OKE AT 60 PSI AIR
08/13/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :* 14 psi TEST IS OK. INSPECTED GAS LINES & PRESSURE TO 3RD & 4TH FLOOR FIREPLACES. OK TO COVER.
08/12/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
07/26/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
07/22/2004 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
07/19/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
07/16/2004 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
07/08/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*/ 1) GAS PIPING 1ST FLOOR EXTERIOR TO ROOM 234, 232 AND 223 3/4" PIPE ? PSI AIR TEST PARTIAL APPROVAL
05/14/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*/ 60 PSI AIR TEST ON 3" SERVICE MAIN FROM METER TO 1¼" DISTRIBUTED TO ALL BLD STUB UPS PARTIAL APPROVAL. 3" RISER IS A CSA LISTED DEVICE.
05/06/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :
See detailed listing on site.| 999*
04/30/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*/ 1) 60 PSI AIR TEST ON 5 PSI SYSTEM INSTALLED AS P.E. PIPING PER PLAN LOOPED PAST 2 1/2" SUPPLY BACK TO METER 2) WILL NEED INFORMATIONPER NOTE ON 4/26/04 INSPECTION 3) WILL NEED TO SEE 2 1/2" PIPING INSTALLED AND TESTED
04/28/2004 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*/ 1) 60 PSI TEST AT TIME OF INSPECTION SHALL BE IN PLACE
04/26/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*/ 60 PSI AIR TEST ON 5 PSI SYSTEM FROM SOUTH WEST 7" STUB UP AT FIRE PLACE, 1¼ STUB UP AT SOUTH WTR HTR AREA, CONTINUES 1¼" TO MY INITIAL ON MEP 1.0 - PARTIAL APPROVAL PENDING LETTER FROM ENGINEER STATING P.E. PIPING IS OK. IN PLACE OF BLK I.P. OR CORRUGATED STAINLESS STEEL.