Permit: T03CM02424

Parcel: 128102930

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM02424

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/02/2004 ELECTRIC - FINAL Approved OK FOR C OF O
12/01/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SERVICE PANELS HAVE BEEN RELABELED TO 1000 AMPS EACH OF 3 SECTIONS
2) LETTER FROM UL DOES NOT GIVE INFORMATION OF WHAT WAS INSPECTED, CHANGED TO, ADDRESS OF SITE AND JOB INVOLVED, MODEL OF SWITCH GEAR INVOLVED. DATE SWITCH GEAR RELABELED AND WHY
11/30/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) LETTER FROM GE ALSO REQUIRED AS WELL AS UL LISTING CHANGE
11/29/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) STILL NEED LETTER ON SWITCH GEAR DERATING
11/24/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) FINISH JOB
11/23/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/19/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) LABEL ELECTRIC ROOMS (ELECTRIC ROOMS) 1, 2, ETC...
2) 4TH AND 3RD FLOOR NEED PANEL NUMBERING
3) 1ST MDP 1AS-2 PANEL ? MISSING
4) NEED LETTER FROM G.E. ON SERVICE RATING
11/03/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/25/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/21/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/19/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) GUEST ROOMS 1ST AND 2ND FLOOR, EXCEPT ROOM 103 (PANEL BOARD). 123, 124, 126, 223, 224 AND 226 NEED ? WORK PRIOR TO
10/19/2004 ELECTRIC - FINAL Partial Approval
10/15/2004 ELECTRIC - FINAL Partial Approval RECALL FOR MON
04/27/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*