Permit: T03CM02424

Parcel: 128102930

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
10/19/2004 ELECTRIC - CABLE DROP Approved
09/17/2004 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/13/2004 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/10/2004 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
09/03/2004 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) IN VIOLATION OF 110-26 (C) EQUIP. RATED 1200 AMPS AND OVER 6' WIDE REQUIRE 2-EXITS 24" WIDE X 6 1/2" FT HEIGHT PER CODE. ALSO IT IS REQUIRED THAT THE EDGE OF THE DOOR FOR EXIT TO START A MINIMUM OF 3 FT. (TABLE 110-26 (A)
09/02/2004 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :INSTALL DOORS WITH LOCKS (2) CANNOT HAVE DRAIN PIPING ABOVE PANELBOARD
04/27/2004 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*