Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T03CM02416
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2003 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000*/ALL CORRECTIONS HAVE BEEN MADE. OK FOR C OF O | |
06/12/2003 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) SHEET METAL DUCT JUST ABOVE SHORT ANGLED WALL HAS BROKEN LOOSE FROM IT'S SUPPORT. RESTRAP DUCT AS NEEDED. LEAVE OUT CEILING TILE IN THEIS AREA AND RECALL FOR INSPECTION. OK FOR TILES EVERYWHERE ELSE. FIRE DAMPER HAS BEEN REPAIRED. SUPPORT EXHAUST DUCT FROM RESTROOM. CANNOT LAY ON GRID. RE-ATTACH WHERE BROKEN LOOSE FROM EXHAUST FAN. LEAVE OUT TILES IN THIS AREA ALSO | |
06/06/2003 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection 0999*/ 1) REPAIR BROKEN LINK IN FIRE DAMPER IN SEPERATION WALL. ELECTRICAL CONDUIT AND WIRES CANNOT PASS THROUGH A FIRE DAMPER. RELOCATE CONDUIT AND WIRES AS NEEDED. REMOVE ANY OBSTRUCTIONS FROM DAMPER. FIRE CAULK ANY PENETRATIONS THRU WALL. STRAP UP ANY LOOSE FLEX DUCT LAYING ON TILES AND GRID. RECALL FOR INSPECTION |