Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/01/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) #2, 4, 6 AND 7 NOT DONE FROM LAST INSPECTION |
| 09/26/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) CORRECT NEGATIVE PITCH ON CONDENSATE LINES 2) WRENCH TIGHTEN A.B.'S AND RED HEADS 3) DRYER VENT SHOULD BE 4" PER PAGE M-1 4) SHIM TRIMMERS WHERE NEEDED 5) STRAP TOP PLATES AT MASTER BEARING 45 DEGREE WALL 6) CREATE 2" CLEARANCE AT FIREPLACE CHIMNEY 7) CORRECT TC CLIP NAILING WHERE NEEDED 8) NEED H.D. IN KITCHEN S.E. CORNER 9) GROUND PANCAKE IN N.E. BED 10) BANG PLATE WIRES SOUTH OF HOMERUNS 11) NEED MID-SPAN CROSS BRACING 12) FIREBLOCK 4 DINING CHASES |