Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T03CM02394
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/16/2003 | BUILDING - FINAL | Approved | ||
10/15/2003 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) LABEL ALL BREAKERS 2) CHANGE 20 AMP BREAKER TO 15 ON #14 WIRE 3) FINISH IRRIGATION WIRING-NO GROUND? 4) REAR EXT. GFI WON'T TRIP 5) SMOKIES NOT INTER-CONNECTED 6) MASTER GFI'S INOPERABLE 7) KITCHEN GFI WON'T TRIP | |
10/14/2003 | BUILDING - FINAL | Denied | IVRS - Inspection 0999* |