Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM02392
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1) ROUGH IN FOR ZEWC INSTALLED PER PLAN COPPER OK. 2) OK TO COVER | |
| 07/01/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) NOT INSTALLED PER PLAN ONLY TOW FIXTURES ON 1/2" COLD WATER. SEE PLAN WATER NOTES. NOTE: PLAN REQUIRES TYPE "L" COPPER | |
| 06/29/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) NOT INSTALLED PER PLAN SEE ISOMETRIC DRAWING. ONLY ON TRAP PER TRAP ARM 2) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE THROUGH WYE BRANCH FITING OR EQUIVALENT SWEEP 3) NO TEST ON ABS 4) THIS MAY NOT BE A COMPLETE LIST. HAVE PLUMBER CHECK ALL WORK 5) POST YOUR ADDRESS SO THAT IT CAN BE SEEN FROM THE STREET |