Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/01/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 07/30/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) SEE NOTES CIRCLED FROM INSPECTION 7/25/03 NOT DONE 2) FRAMING WILL BE APPROVED WHEN ALL TRADES ARE COMPLETE 3) NEXT FAILURE WILL RESULT IN A REFEE 4) DWV'S AND WATER LINES PASSED TEST |
| 07/25/2003 |
FRAMING |
|
Denied |
1) SEAL ELECTRIC RACEWAY 2) NAILER AT GLUE LAM GARAGE NOT NAILED PER PLAN, BOTH SIDES 3) KING STUD MISSING AT LEFT SIDE SLIDING GLASS DOOR 4) SECURE WATER LINES ABOVE ENTRY 5) NAIL PROTECT WATER LINES AT POWDER ROOM AND VENT 6) SECURE WATER LINES IN POWDER ROOM 7) MOVE RETURN DUCT AWAY FROM WATER HEATER FLUE 8) SMOKE DETECTORS MUST BE 18" AWAY FROM CORNERS 9) PLYWOOD AT ATTIC PLATFORM GRAIN RUNNING WRONG WAY 10) NAIL PROTECT ELECTRIC AT LAUNDRY ROOM 11) INSULATE BEHIND TUB 12) NAIL PROTECT ELECTRIC AT CLOSET IN BATHROOM 2ND FLOOR 13) RETURN VENT NOT BLOCKED 2ND FLOOR 14) HOLDOWNS NOT INSTALLED 15) SHUT OFF VALVE AT WATER HEATER LEAKING |
| 07/24/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) SUPERINTENDENT TOLD ME NOT TO INSPECT |