Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/05/2003 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FOR SHEET ROCK. WILL CHECK VENT EXTENSION ON FINAL |
| 09/03/2003 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) HORIZONTAL SECTION OF WATER HEATER VENT CANNOT EXCEED 75 PERCENT OF TOTAL VENT HEIGHT |
| 08/28/2003 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/1) OFFSET ON WATER HEATER VENT CANNOT 60 DEGREES. HORIZONTAL SECTION OF VENT CANNOT EXCEED 75% OF TOTAL VENT HEIGHT. 2) INSTALL CONDENSATE DRAIN. RECALL FOR INSPECTION. |