Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T03CM02340
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/14/2003 | MECHANICAL - INTERMEDIATE | Approved | ||
08/11/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) SUPPLY CUT SHT. W/ DAMPER INSTALLATION INSTRUC. WHAT TYPE DAMPER USED? 2) REMOVE 2 FIRE DAMPER RETAINING ANGLES TO CK PENETRATIONS. 3) EXIST. FIRE DAMPERS ADJOINING RATED(?)CORRIDOR. NEED TO RE-ATTACH EXISTING ANGLES IN PROPER POSITION. 4) ADVISE MALL THAT REAR EAST WALL HAS NO INTEGRITY, TOP OF WALL UNDER LID. WHY IS OPENING FIRE DAMPERS. |