Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM02340

Parcel: 10511061R

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T03CM02340

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2003 MECHANICAL - INTERMEDIATE Approved
08/11/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) SUPPLY CUT SHT. W/ DAMPER INSTALLATION INSTRUC. WHAT TYPE DAMPER USED? 2) REMOVE 2 FIRE DAMPER RETAINING ANGLES TO CK PENETRATIONS. 3) EXIST. FIRE DAMPERS ADJOINING RATED(?)CORRIDOR. NEED TO RE-ATTACH EXISTING ANGLES IN PROPER POSITION. 4) ADVISE MALL THAT REAR EAST WALL HAS NO INTEGRITY, TOP OF WALL UNDER LID. WHY IS OPENING FIRE DAMPERS.