Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/05/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) NOTE: OPTICAL, PHOTO, CAMERA AND HEARING |
| 08/04/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FINISH SUPPORTING MANUFACTURED WIRING SYSTEMS IN CAMERA 2) ROOMS A & B, NEED TO SEE HOOK-UP 3) NEED TO SUPPORT 1 1/2" CONDUIT FROM PANEL "FLB" 4) FILL UNUSED OPENINGS IN GUTTER 5) OK PANEL "FLB", OK ABOVE CEILING |
| 08/01/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) INDEPENDENTLY SUPPORT M/C CABLE 300-31 2) SUPPORT CONDUIT AS PER CODE 3' + 10' 3) FIXTURE TO BE ATTACHED TO GRID 4) TIGHTEN LOOSE FITTINGS 5) CHECK BOX FILL 6) FILL UNUSED OPENINGS IN JUNCTION BOXES |