Permit: T03CM02284

Parcel: 123023060


Addresses:

2510 E HAMPTON ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/06/2004 FRAMING Approved IVRS - Inspection 0000*
02/05/2004 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) PLAN CALLS FOR LAV TO VENT TO ROOF IF AIR ADMITTANCE VALVE IS TO BE USED THEN PLAN MUST BE REVISED AND APPROVED 2) NAIL PROTECT ALL WIRES WITHIN 1 1/4" OF WALL SURFACE WITH 1/16" STEEL 3) OK TO DRYWALL ALL BUT MECHANICAL ROOM AND BATH ROOM SOUTH EAST WALL BY WIRES
02/04/2004 FRAMING Denied IVRS - Inspection 0999*/1) COMPLETE FRAMING AT WATER HEATER CLOSET 2) FIRE BLOCK AT NORTH WALL 3) NO WATER AT DWV 4) 6" CLEARANCE FROM WATER LINE ?
01/30/2004 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) ALL PARTIALS FOR GARAGE AND LAUNDRY ONLY