Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM02275
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
09/12/2003 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) OK TO INSULATE 2) FROM LAST INSPECTION CONDENSATE CANNOT CONNECT TO WASHER TAIL PIECE UNLESS YOU HAVE AN ACCESS PANEL, BOTH ENDS TO BE ACCESSIBLE 3) NO WATER IN DW VENT PIPE | |
09/10/2003 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) OVERSPAN STUD KITCHEN, WING WALL AT REAR DOOR AND AT TUB 2) STIFF LEG KITCHEN DROP CEILING TO ROOF FOR SUPPORT AND HALL 3) TUB, BACKING, SIDES OF TUB 4) NAIL HOLES HANGERS, ANGLED HEADER 5) TUB DRAIN WEST WALL, KEEP OUTLET OUT OF TUB AREA 6) BLOCK ALL REGISTERS 7) WATER HEATER FLUE/COMBUSTIOJN RELIEF-10' FROM FRESH AIR MAKE UP (IF WATER HEATER IS GAS) 8) CONDENSATE TO A LAV TAIL PIECE, TO DAY LIGHT OR 1" AIR GAP ONLY 9) DRAIN, WASTE AND VENT WATER TEST REQUIRED 10) GAS PRESSURE TEST OK, POTABLE WATER-OK |