Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/15/2003 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 08/14/2003 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0250*/1) SEISMIC WIRES MUST BE ATTACHED TO TRACK LIGHTS. TWO PER PIECE. 2) THE 2X4 TROFFERS MUST BE SECURED TO THE GRID WITH SCREWS OR CLIPS MADE FOR THE PURPOSE. 3) CHECK 2X4 TROFFERS FOR MISSING SEISMIC WIRES. |