Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/30/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/02/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) ENGINEER TO CLARIFY THE TERM WATERPROOF USED FOR HANDHOLE SPLICES. IS THERE A TYPE OR LISTED KIT? OR CONTRACTOR TO USE LISTED SPLICE KITS FOR WATERPROOF PROTECTION. 2) HANDHOLE DETAILS CALL FOR HANDHOLE COVER TO BE 1" ABOVE GRADE. |