Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T03CM02218
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000*/ 1) OK ABOVE CEILING | |
08/18/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) SUPPORT M/C CABLE AS PER CODE 334.10 ALSO USE CURRENT SIZED STRAPS 2) IF SUPPORT WIRE PRE USED THEY MUST BE ATTACHED AT BOTH ENDS 300.11 4) ATTACH FIXTURES TO GRID ROOM #103 |