Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM02218
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2003 | ELECTRIC - INTERMEDIATE | Approved | ||
07/23/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/HALLWAYS. NOTES: 1) PROVIDE ACCESS HATCHES FOR J-BOXES ABOVE HARD CEILINGS, ROOM 101, CORRIDOR. 2) OK WALLS, CORRIDORS. | |
07/21/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) SUPPORT M/C CABLE WITHIN 12" OF BOXES AND BURY 6'. 334-10. 2) JUNCTION BOXES TO BE ACCESSABLE AFTER DRYWALL. 3) PROTECT M/C CABLE W @ HANELL? OR REMOVE OUT OF CHANELL. 300-4. 4) PLEASE PREVENT DIE ELECTRIC CIRCUIT. OK ROOMS # 102-119 ONLY WALLS. | |
07/18/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*/ NOTES: 1) NEED APPROVAL FROM ARCH. FOR USE OF MC CABLE. 2) SUPPORT MC IT APPROVED BY ARCH. PER ART. 334-10 N.E.C. SUPPORT TO STRUCTURE. DO NOT SUPPORT MC TO OTHER RACEWAYS. 3) PLEASE HAVE CONTR. ON SITE TO MEET WITH ELEC. INSP. HAVE QUESTIONS. |