Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/18/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ OK FINAL |
| 07/17/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CONDUIT AND FITTING TO CUTTER TO BE INSTALLED CORRECTLY 2) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS IN DISCONNECT WITH AN APPROVED DEVICE 373.2 3) AN APPROVED EXTENDER RING IS NEEDED WHERE MORE THAN 1/4" FROM BOX TO SURFACE 370.20 4) SPLIT BOLTS ARE LISTED FOR ONLY A RUN AND A TRAP (2 CONDUCTORS) 5) CLEAN SURFACE BEHIND GROUND BAR 250.10 |
| 07/14/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |