Permit: T03CM02163

Parcel: 12113005A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/18/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ OK FINAL
07/17/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) CONDUIT AND FITTING TO CUTTER TO BE INSTALLED CORRECTLY 2) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS IN DISCONNECT WITH AN APPROVED DEVICE 373.2 3) AN APPROVED EXTENDER RING IS NEEDED WHERE MORE THAN 1/4" FROM BOX TO SURFACE 370.20 4) SPLIT BOLTS ARE LISTED FOR ONLY A RUN AND A TRAP (2 CONDUCTORS) 5) CLEAN SURFACE BEHIND GROUND BAR 250.10
07/14/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*