Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/17/2003 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 07/14/2003 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 07/10/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/08/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* 1) FIXTURES TO BE ATTACHED TO NEW GRID WORK-ENTIRE PROJECT APPEARS TO HAVE NEW GRID. 2)M/C CABLE TO BE SUPPORTED WITH IN 12" OF FIXTURES AND BOXES. 3) WHERE IS REVISION FOR ROOM 14 LIGHTING. 4) FINISH BOX MAKE-UP. 5) BOX TO BE GROUNDED. |