Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/24/2004 |
ELECTRIC - FINAL |
|
Approved |
OK PER PHONE CONVERSATION WITH STEVE LONG |
| 03/19/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 03/18/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* OK FOR TEMP C/O |
| 03/17/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 03/15/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/10/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*/ 1) SUPPORT CONDUITS BELOW TERM CAP. 2) LABEL BREAKERS . 3) MAIN TO HAVE MANUFACTURERS HOLD DOWN DEVICE. 4) JUNTION BOX TO BE LARGE ENOUGH FOR CONTACTOR AND CONDUCTORS. 5) BOND JUNCTION BOX. 6) NO WORK PROGRESS ON POLE FROM INSP, 1/8/04. A REFEE HAS BEEN ASSESSED. |