Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/24/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 03/09/2004 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ FINISH POLES AS DISCUSSED. |
| 02/20/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 02/18/2004 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 01/27/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 01/12/2004 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |
| 01/08/2004 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) GROUNDING ELECTRODE TO BE CONNECTED TO POLE AND BONDED TO EQUIPMENT GROUNDING CONDUCTOR (BLUE WIRE NUT NOT LISTED FOR LARGER THATN #8) 2) CONDUCTOR COLOR PHASING TO BE CONTINOUS THRU-OUT NOT CHANGING COLORS AT POLES 3) PLEASE PROVIDE ACCESS TO HEADS FOR INSPECTION AS DISCUSSED BEFORE POLES WERE STOOD |