Permit: T03CM02129

Parcel: 110055390

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM02129

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
12/03/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
11/26/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) M/C CABLE TO BE SUPPORTED AS PER CODE 334.10, 12" + 6'
11/24/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK SERVICE OK OWNERS METER ONLY 2) SOFFIT CANS NOT ACCESSIBL-COVERED WITHOUT INSPECTION 3) SENT TO TEP ON 1125AM
11/21/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
11/19/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
11/14/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000* PLANS NEED TO BE REFLECTIVE OF WORK INSTALLED, ALSO COMPLETE PLANS FOR SERVICE CONDUCTORS.
07/02/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*