Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/02/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 06/30/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) APPROVED EXTENDER RINGS ARE WEEEDED WHERE MORE THATN 1/4" FROM BOX TO SURFACE 370.20-METAL NOT APPROVED 2) PLEASE REVISE CIRCUIT DIRECTORY. DOES NOT MATCH PLANS 3) TIGHTEN LOOSE SEAL TITE FITTINGS AND SUPPORT SEAL TITE 4) EXHAUST HOOD NOT AS PER PLANS-PLEASE HAVE PLANS REVISED OR INSTALL AS PER PLANS. PLAN REVISIONS TO BE STAMPED WITH APPROVAL |