Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/11/2004 |
FRAMING |
|
Approved |
|
| 04/07/2004 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) NAIL SIDING 2) PROPERLY PROVIDE BIRD BLOCKS |
| 11/04/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) HEADERS IN CORRECTLY INSTALLED 2) STAPLE ROMEX WITHIN 12" BOXES 3) GROUND ALL METAL ELECTRIC BOXES 4) TIGHTEN PLATE NUTS ON BOLTS 5) INSTALL BANG PLATE NAIL PROTECTION AT ELECTRIC HOLES IN STUDS, PLATES 6) PLAN CALLS FOR 2" X 8" RAFTERS AT 16" SPACING AND 2" X 4" STUDS ON 10" SPACING 7) HAVE ELECTRIC JUNCTION BOX ACCESSIBLE 8) USE TECO NAILS, NOT DRYWALL SCREWS INTO H2.5 FASTENERS 9) INSTALL WIRING FOR SMOKE DETECTOR 10) INSTALL ELECTRICAL OUTLETS AND SWITCHES TO PALN 11) NAIL SIDING TO STUDS 12) STOPPED INSPECTION |