Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM02092
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/11/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) PLUMBING FIANL IS OK 2) OK FOR C OF O | |
07/09/2003 | PLUMBING - FINAL | Denied | 1) GREASE TRAP OUTLET CANNOT BE REDUCED. THERE CAN BE NO OBSTRUCTION OF FLOW SECTION: 311.5 94 UPC 2) CANNOT HAVE FLAT FACED BUSHING IN A HORIZONTAL POSITION 311.5 94 UPC 3) BACKFLOW PREVENTER FOR SODA MACHINE. MUST BE A 009 WITH DISCHARGE DRAIN 4) ICE MACHINE REQUIRE A 007 BACKFLOW PREVENTOR 5) H.C. MENS WATER CLOSET HANDLE MUST BE ON OPEN SIDE OF ROOM (ADA SPECS) 6) H.C. LAVATORY (MENS) HEIGHT MAXIMUM IS 34" A.F.F. 7) HOSE BIB IN MENS RESTROOM REQUIRES A VACCUM BREAKER |