Permit: T03CM02092

Parcel: 13348128D

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03CM02092

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/11/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 1) PLUMBING FIANL IS OK 2) OK FOR C OF O
07/09/2003 PLUMBING - FINAL Denied 1) GREASE TRAP OUTLET CANNOT BE REDUCED. THERE CAN BE NO OBSTRUCTION OF FLOW SECTION: 311.5 94 UPC 2) CANNOT HAVE FLAT FACED BUSHING IN A HORIZONTAL POSITION 311.5 94 UPC 3) BACKFLOW PREVENTER FOR SODA MACHINE. MUST BE A 009 WITH DISCHARGE DRAIN 4) ICE MACHINE REQUIRE A 007 BACKFLOW PREVENTOR 5) H.C. MENS WATER CLOSET HANDLE MUST BE ON OPEN SIDE OF ROOM (ADA SPECS) 6) H.C. LAVATORY (MENS) HEIGHT MAXIMUM IS 34" A.F.F. 7) HOSE BIB IN MENS RESTROOM REQUIRES A VACCUM BREAKER