Permit: T03CM02077

Parcel: 12701008A


Addresses:

5285 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T03CM02077

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2004 PLUMBING - SEWER HCS CONNECT Approved
11/04/2003 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ WATER TEST OK FROM BLDG TO M.H. #5. OK TO BACKFILL SITE OF INSPECTION.
10/20/2003 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ 1) VACCUM TEST OK ON M-H #4 AND #5 2) AIR TEST OK M-H #1 AND #2, M-H #2 AND #3, M-H #3 AND #4, M-H #4 AND #5 3) NEED DATA ON M-H VERIFICATION OF GRADE. COMPLETE ? AT M-H #1
10/17/2003 PLUMBING - SEWER HCS CONNECT Partial Approval COMPLETE UP TO M.H. #5 - CONTRACTOR WILL TEST AT LATER DATE. OK TO COVER. NEED DATA ON M.H.
10/16/2003 PLUMBING - SEWER HCS CONNECT Partial Approval 1) 126' EAST OF M-H #4 OK TO BACKFILL. WILL REQUIRE VERIFICATION OF GRADE VACCUM TEST ON M-H'S TESTING AT LATER DATE. OK TO COVER
10/15/2003 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ UP TO M-H #4 OK TO COVER SUBJECT TO VERIFICATION OF GRADE. VACUUM TEST ON M-H.
10/14/2003 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ APPROX. 165' - SUBJECT TO TESTING./ VACUUM TEST ON MANHOLES 1,2,3 OK. NEEDS LISTING ON MH FROM HAYDEN.
10/13/2003 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ 65' EAST OF MH. #3 - CONTRACTOR WILL PROVIDE VERIFICATION OF GRADE TEST AT LATER DATE. ALSO VACUUM TEST AT LATER DATE.
10/10/2003 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*
10/09/2003 PLUMBING - SEWER HCS CONNECT Partial Approval 1) G5 TO M-H #3 OK TO COVER WILL REQUIRE VERIFICATION OF GRADE 2) CONTRACTOR WILL TEST AT LATER DATE 3) WILL REQUIRE VACCUM TEST ON M-H'S
10/08/2003 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ WILL REQUIRE VERIFICATION OF GRADE. CONTRACTOR WILL TEST AT LATER DATE.
10/07/2003 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection 0000*/ REVISED APPROVED PLAN ON JOB BY WILDAV.
10/06/2003 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection 0000*/ FROM M.H.? APPROX 125' SOUTH - COVERED WITHOUT INSP. - CONTRACTOR WILL UNCOVER BEFORE FINAL IS GIVEN. TALKED WITH MIKE. WILL REQUIRE VERIFICATION OF GRADE ON COMPLETE SEWER AND TESTING BEFORE FINAL IS GIVEN. VACUUM TEST REQUIRED ON M.H.'S. 10/06/03 - 3:00 PM - 28' SDR 35 - NOT READY. UNABLE TO COMPLETE INSPECTION. NO APPROVED REVISED PLANS ON JOB. APPROVED PLAN CALLS FOR M.H. #2.
10/05/2003 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection 0999*