Permit: T03CM02068

Parcel: 141173320

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T03CM02068

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
07/01/2003 FRAMING Approved IVRS - Inspection 0000*
06/30/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) DWV'S AT WATER LINES FAILED TEST 2) GAS PRESSURE TEST AT 8.5 PSI, 10 PSI MINIMUM REQUIRED 30 NAIL PROTECT COPPER LINE IN GARAGE 4) STOPPED INSPECTION CALL BACK WHEN READY