Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM02062
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
07/08/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* 1) INSULATE RETURN PLUMBING. 2) CONNECT DUCT TO EXHAUST FAN IN DARK ROOM. 3) STRAP UP FLEX DUCT TO EXAM ROOM #1. 4) TERMINATE CONDENSATE INTO AN APPROVED LOCATION. BLOCK & CLAMP PVC ON ROOF & PAINT WITH LATEX PAINT. 5) PROVIDE A FILTER IN OUTSIDE AIR INTAKE. O.K. FOR TEMP. C/O. | |
07/03/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* |