Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/22/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/21/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) SOME ITEMS NEED TO BE BUTTONED UP |
| 07/09/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/OK PHASE 1 SUBJECT TO OTHER INSPECTIONS AND A BOND MAY BE NEEDED. OK AS DISCUSSED. |
| 07/08/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* FINISH #1,3 & 5 OF PREVIOUS INSP |
| 07/03/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) APPROVED EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" FROM BOX TO SURFACE 370-2 2) NEED A REVISED CIRCUIT DIRECTORY. 3) PROTECT CONDUCTORS AT OPENING FOR X-RAY EQUIPMENT & FILL ??OPENING. 4) SHEET METAL SCREW NOT ALLOWED FOR GROUNDING 250-8. 5) WE HAVE 1 CIRCUIT TO DENTAL CHAIRS-PLANS CALL FOR 2 CIRCUITS. |