Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM02062
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
08/21/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) SOME ITEMS NEED TO BE BUTTONED UP | |
07/09/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/OK PHASE 1 SUBJECT TO OTHER INSPECTIONS AND A BOND MAY BE NEEDED. OK AS DISCUSSED. | |
07/08/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* FINISH #1,3 & 5 OF PREVIOUS INSP | |
07/03/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1) APPROVED EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" FROM BOX TO SURFACE 370-2 2) NEED A REVISED CIRCUIT DIRECTORY. 3) PROTECT CONDUCTORS AT OPENING FOR X-RAY EQUIPMENT & FILL ??OPENING. 4) SHEET METAL SCREW NOT ALLOWED FOR GROUNDING 250-8. 5) WE HAVE 1 CIRCUIT TO DENTAL CHAIRS-PLANS CALL FOR 2 CIRCUITS. |