Permit: T03CM02056

Parcel: 141172580

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T03CM02056

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
08/07/2003 FRAMING Approved
06/24/2003 FRAMING Partial Approval IVRS - Inspection 0000*OK TO INSULATE 1)LAST HOUSE TO HAVE M.A.S. MUDSILL ON SHEARWALLS WITHOUT APPROVAL. PROBLEM: SHEAR WALL IS ATTACHED PRIOR TO BEING BROUGHT TO JOB SITE. REQUIRES A HOLE TO BE KNOWCKED OUT TO ATTACH THE STRAP. STRAPS AREN'T BEING INSTALLED CORRECTLY TO THE B/PLATE. 52 MODEL 10' SHEAR WALL; 5 HOLES AT BOTTOM OF SHEAR
06/20/2003 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) AT FRONT GABLE TRUSS SECURE TO TOP PLATE WITH CLIPS LIVING GABLE 2) NEED 3.5'S AT GARAGE LEDGER 1/A2 3) MASTER BEDROOM STUD OVER SPAN 4) MASTER BEDROOM SHEAR BOTTOM PLATES NOT SECURE PLATE CLIPS NOT INSTALLED CORRECTLY 5) FRONT DOOR PLATE NOT SECURE 6) NEED DWV TEST 7) EXHAUST FAN DAMPERS MISSING 8) SECURE WATER LINE FRONT BATH 9) ROMEX LOOP AT HALL RETURN DUCT ? 10) USE CORRECT NAILS IN GARAGE HANGERS 11) SHEAR TRANSFER NOT COMPLETE AT TOP PLATE GARAGE TO HOUSE 12) HOLE IN KITCHEN DINING FLOOR