Permit: T03CM02055

Parcel: 141172570

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T03CM02055

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
06/23/2003 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
06/10/2003 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection 0000*/ 1) NO HOLDOWNS REAR OF HOUSE NOT NAILED TO TWO KING STUDS REPLACE WILL CHECK AT INTERMEDIATES 2) CHECK OVERSPAN STUDS AT GARAGE AND NORTH WEST CORNER
06/06/2003 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) FRONT POP OUT NOT NAILED 2) NEED A.B. AT SOUTH SHOWER SPLICE IN B/PLATE 3) OSB TURNED THE WRONG WAY AT FRONT DOUBLE HIP TO VERTICAL WALL 4) WHAT SIZE NAIL WAS USED IN AHUGS-26-2 HANGER ? NEED HEADER SIZE GARAGE MAN DOOR 6) NEED TRUSS SHOP DRAWINGS 7) AT NEXT INSPECTION NEED IN WRITING STRUCTUAL INFO; FOR SHEAR TRANSFER AND A SET OF HEADER SIZES FOR ALL MODELS