Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2004 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 07/01/2004 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/23/2004 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NO PLANS/PERMIT 2) NO UFER APPROVED 3) MUST DRIVE GROUND RODS 4) TAPE ENDS OF WIRES INSIDE PANEL BOX AND SECURE AWAY FROM LIVE BUS BARS |